GE L60 Instruction Manual page 581

Line phase comparison system, ur series
Hide thumbs Also See for L60:
Table of Contents

Advertisement

APPENDIX B
Table B–10: MODBUS MEMORY MAP (Sheet 25 of 57)
ADDR
REGISTER NAME
67F2
Trip Reclose Input6
67F3
Trip Force 3-Pole
67F4
Trip Pilot Priority
67F5
Breaker Phase A Open
67F6
Breaker Phase B Open
67F7
Breaker Phase C Open
67F8
Trip Events
67F9
Reverse Fault Operand
67FA
Trip Delay On Evolving Faults
67FB
Trip Seal-In Delay
67FC
Trip Reset
67FD
Start Timer Zone 2 Phase Input 1
67FE
Start Timer Zone 2 Phase Input 2
67FF
Start Timer Zone 2 Ground Input 1
6800
Start Timer Zone 2 Ground Input 2
6801
Reserved (5 items)
Open Pole Detect (1P) (Read/Write Setting)
6820
Open Pole Function
6821
Open Pole Block
6822
Open Pole Voltage Supervision
6823
Open Pole Current Pickup
6824
Open Pole Target
6825
Open Pole Events
6826
Open Pole Line XC0
6828
Open Pole Line XC1
682A
Open Pole Remote Current Pickup
682B
Open Pole Detection
682C
Open Pole Mode
682D
Reserved (3 items)
Autoreclose 1P 3P (Read/Write Setting)
6890
Autoreclose Mode
6891
Autoreclose Maximum Number of Shots
6892
Autoreclose Block Breaker 1
6893
Autoreclose Close Time Breaker 1
6894
Autoreclose Breaker Manual Close
6895
Autoreclose Function
6896
Autoreclose Block Time Manual Close
6897
Autoreclose 1P Initiate
6898
Autoreclose 3P Initiate
6899
Autoreclose 3P TD Initiate
689A
Autoreclose Multi-Phase Fault
689B
Autoreclose Breaker 1 Pole Open
689C
Autoreclose Breaker 3 Pole Open
689D
Autoreclose 3-Pole Dead Time 1
689E
Autoreclose 3-Pole Dead Time 2
689F
Autoreclose Extend Dead T1
68A0
Autoreclose Dead T1 Extension
68A1
Autoreclose Reset
68A2
Autoreclose Reset Time
68A3
Autoreclose Breaker Closed
68A4
Autoreclose Block
68A5
Autoreclose Pause
68A6
Autoreclose Incomplete Sequence Time
GE Multilin
RANGE
0 to 65535
0 to 65535
0 to 65.535
0 to 65535
0 to 65535
0 to 65535
0 to 1
0 to 65535
0 to 65.535
0 to 65.535
0 to 2
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 1
0 to 1
0 to 65535
0 to 1
0 to 30
0 to 2
0 to 1
300 to 9999.9
300 to 9999.9
0 to 30
0 to 1
0 to 1
0 to 1
0 to 3
1 to 4
0 to 65535
0 to 655.35
0 to 65535
0 to 1
0 to 655.35
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 655.35
0 to 655.35
0 to 65535
0 to 655.35
0 to 65535
0 to 655.35
0 to 65535
0 to 65535
0 to 65535
0 to 655.35
L60 Line Phase Comparison System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F300
---
1
F300
s
0.001
F001
---
1
F300
---
1
F300
---
1
F300
---
1
F102
---
1
F300
s
0.001
F001
s
0.001
F001
---
1
F609
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F001
---
1
F102
---
1
F300
---
1
F102
pu
0.001
F001
---
1
F109
---
1
F102
ohms
0.1
F003
ohms
0.1
F003
pu
0.001
F001
---
1
F608
---
1
F607
---
1
F001
---
1
F080
---
1
F001
---
1
F300
s
0.01
F001
---
1
F300
---
1
F102
s
0.01
F001
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
s
0.01
F001
s
0.01
F001
---
1
F300
s
0.01
F001
---
1
F300
s
0.01
F001
---
1
F300
---
1
F300
---
1
F300
s
0.01
F001
DEFAULT
0
0
0
0
0
B
0
0 (Disabled)
0
0
0
0 (Pole Curr OR
Custom)
0
0
0
0
0
0 (Disabled)
0
0 (Disabled)
50
0 (Self-reset)
0 (Disabled)
99999
99999
50
0 (I AND V AND
CBaux)
0 (Accelerated)
0
0 (1 & 3 Pole)
2
0
10
0
0 (Disabled)
1000
0
0
0
0
0
0
50
120
0
50
0
6000
0
0
0
500
B-33