6 ACTUAL VALUES
PATH: ACTUAL VALUES
METERING
TRACKING FREQUENCY
The tracking frequency is displayed here. The frequency is tracked based on the selection of the reference source with the
FREQUENCY AND PHASE REFERENCE
Power System section of chapter 5 for additional details.
PATH: ACTUAL VALUES
METERING
FLEXELEMENT 1
The operating signals for the FlexElements™ are displayed in pu values using the following definitions of the base units.
Table 6–2: FLEXELEMENT™ BASE UNITS
BREAKER ARCING AMPS
(Brk X Arc Amp A, B, and C)
DCmA
FAULT LOCATION
FREQUENCY
PHASE ANGLE
POWER FACTOR
RTDs
SOURCE CURRENT
SOURCE POWER
SOURCE VOLTAGE
SYNCHROCHECK
(Max Delta Volts)
PATH: ACTUAL VALUES
METERING
IEC 61850
GOOSE ANALOGS
MESSAGE
MESSAGE
MESSAGE
GE Multilin
TRACKING FREQUENCY
TRACKING FREQUENCY:
60.00 Hz
setting in the
SETTINGS
FLEXELEMENTS
FLEXELEMENT 1(8)
FLEXELEMENT 1
OpSig: 0.000 pu
2
BASE = 2000 kA
× cycle
BASE = maximum value of the
DCMA INPUT MAX
under the +IN and –IN inputs.
BASE = Line Length as specified in Fault Report
f
= 1 Hz
BASE
ϕ
= 360 degrees (see the UR angle referencing convention)
BASE
PF
= 1.00
BASE
BASE = 100°C
I
= maximum nominal primary RMS value of the +IN and –IN inputs
BASE
P
= maximum value of V
BASE
BASE
V
= maximum nominal primary RMS value of the +IN and –IN inputs
BASE
V
= maximum primary RMS value of all the sources related to the +IN and –IN inputs
BASE
IEC 61850 GOOSE ANALOGS
ANALOG INPUT
1
0.000
ANALOG INPUT
2
0.000
ANALOG INPUT
3
0.000
↓
ANALOG INPUT 32
0.000
L60 Line Phase Comparison System
6.3.4 TRACKING FREQUENCY
SYSTEM SETUP
POWER SYSTEM
setting for the two transducers configured
× I
for the +IN and –IN inputs
BASE
6.3.6 IEC 61580 GOOSE ANALOG VALUES
6.3 METERING
menu. Refer to the
6.3.5 FLEXELEMENTS™
6-17
6