Download  Print this page

GE L60 Instruction Manual Page 360

Line phase comparison system, ur series.
Hide thumbs
   
1
2
Table of Contents
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
173
174
175
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
226
227
228
229
230
231
232
233
234
235
236
237
238
239
240
241
242
243
244
245
246
247
248
249
250
251
252
253
254
255
256
257
258
259
260
261
262
263
264
265
266
267
268
269
270
271
272
273
274
275
276
277
278
279
280
281
282
283
284
285
286
287
288
289
290
291
292
293
294
295
296
297
298
299
300
301
302
303
304
305
306
307
308
309
310
311
312
313
314
315
316
317
318
319
320
321
322
323
324
325
326
327
328
329
330
331
332
333
334
335
336
337
338
339
340
341
342
343
344
345
346
347
348
349
350
351
352
353
354
355
356
357
358
359
360
361
362
363
364
365
366
367
368
369
370
371
372
373
374
375
376
377
378
379
380
381
382
383
384
385
386
387
388
389
390
391
392
393
394
395
396
397
398
399
400
401
402
403
404
405
406
407
408
409
410
411
412
413
414
415
416
417
418
419
420
421
422
423
424
425
426
427
428
429
430
431
432
433
434
435
436
437
438
439
440
441
442
443
444
445
446
447
448
449
450
451
452
453
454
455
456
457
458
459
460
461
462
463
464
465
466
467
468
469
470
471
472
473
474
475
476
477
478
479
480
481
482
483
484
485
486
487
488
489
490
491
492
493
494
495
496
497
498
499
500
501
502
503
504
505
506
507
508
509
510
511
512
513
514
515
516
517
518
519
520
521
522
523
524
525
526
527
528
529
530
531
532
533
534
535
536
537
538
539
540
541
542
543
544
545
546
547
548
549
550
551
552
553
554
555
556
557
558
559
560
561
562
563
564
565
566
567
568
569
570
571
572
573
574
575
576
577
578
579
580
581
582
583
584
585
586
587
588
589
590
591
592
593
594
595
596
597
598
599
600
601
602
603
604
605
606
607
608
609
610
611
612
613
614
615
616
617
618
619
620
621
622
623
624
625
626
627
628
629
630
631
632
633
634
635
636
637
638
639
640
641
642
643
644
645
646
647
648
649
650
651
652
653
654
655
656
657
658
659
660
661
662
663
664
665
666
667
668
669
670
671
672
673
674
675
676
677
678
679
680
681
682
683
684
685
686
687
688
689
690
691
692
693
694
695
696
697
698
699
700
701
702
703
704
705
706
707
708
709
710
711
712
713
714
715
716
717
718
719
720
721
722

Advertisement

5.6 CONTROL ELEMENTS
TRIP 1-POLE INPUT-1 to TRIP 1-POLE INPUT-6: These settings are used to select an operand representing a fault
condition that is desired to initiate a single pole trip-and-reclose if the fault is single phase to ground (for example, dis-
tance zone 1). Use a FlexLogic™ OR-gate if more than six inputs are required. The inputs do not have to be phase-
specific as the phase selector determines the fault type.
The
AR FORCE 3-P TRIP
operand calls for a three-pole trip if any protection element configured under
open pole detector provides blocking inputs to distance elements, and therefore the latter will reset immediately after
the
operand is asserted. For other protection elements used in single-pole tripping, the user must ensure
TRIP 1-POLE
they will reset immediately after tripping, otherwise the fact that they are still picked up will be detected as an evolving
fault and the relay will trip three-poles. For example, if high-set phase instantaneous overcurrent is used (
"
PHASE IOC1 OP
INPUT X:
rent element. In this way, after tripping phase A, the phase a instantaneous overcurrent element is forced to reset.
Phases B and C are still operational and can detect an evolving fault as soon as 8 ms after tripping phase A. Neutral
and negative-sequence instantaneous overcurrent elements shall be blocked from the
unless the pickup setting is high enough to prevent pickup during single-pole reclosing.
TRIP RECLOSE INPUT-1 to TRIP RECLOSE INPUT-6: These settings select an operand representing a fault condi-
tion that is desired to initiate three pole reclosing (for example, phase distance zone 1). Use a FlexLogic™ OR-gate if
more than six inputs are required. These inputs will also include the
which are intended to initiate three-pole reclosing in situations where single-pole tripping commands are changed to
three-pole tripping commands. This may happen in cases where the phase selector identifies a multi-phase fault or the
AR FORCE 3P TRIP
TRIP SEAL-IN DELAY: This setting specifies the minimum time that trip command signals are maintained to provide
sufficient time to open the breaker poles. If a value of "0" is specified, then the output signal is reset once the protection
elements initiating the trip are reset. If a value other than "0" is specified, then the protection elements must reset and
5
the timer initiated at the first trip command must expire.
TRIP RESET: This setting selects the option to reset the trip latches. If "Pole Curr OR Custom" is chosen, then the
OPEN POLE CURRENT PKP
ers should be set appropriately. Both the "Current" and "CBaux" options can be complimented by custom conditions
using the
BKR ΦA OPEN
tion can be applied to reset trip output latches.
START TMR Z2PH Inp1 and START TMR Z2PH Inp2: These settings select an operand that will start the phase dis-
tance zone 2 timer to avoid a trip delay if the fault evolves from one type to another type (for example, from a single-
line–to-ground fault to a multi-phase fault) or from one zone of protection to another zone of protection (for example,
from zone 3 to zone 2). For instance, the
operand could be assigned to either of these settings. Use a FlexLogic OR-gate if more than two inputs are required.
Refer to phase distance logic diagrams for additional information.
START TMR Z2GR Inp1 and START TMR Z2GR Inp2: These settings select an operand that will start the ground dis-
tance zone 2 timer to avoid a trip delay if the fault evolves from one zone of protection to another zone of protection (for
example, from zone 3 to zone 2). For instance, the
settings. Use a FlexLogic OR-gate if more than two inputs are required. Refer to ground distance logic diagrams for
additional information.
TRIP FORCE 3-POLE: Selects an operand that will force an input selected for single pole operation to produce a three
pole operation. The
figurations or conditions which require such operations may be considered as well.
TRIP PILOT PRIORITY: This setting is used to set an interval equal to the inter-relay channel communications time,
plus an appropriate margin, during which outputs are not asserted. This delay permits fault identification information
from a remote terminal to be used instead of local data only.
REVERSE FAULT: This setting should be used to guarantee accuracy of single-pole tripping under evolving external to
internal faults. When a close-in external fault occurs, the relay is biased toward very fast operation on a following inter-
nal fault. This is primarily due to depressed voltages and elevated currents in response to the first, external fault. The
phase selector may exhibit some time lag compared to the main protection elements. This may potentially result in a
spurious three-pole operation on a single-line-to-ground internal fault. Delaying tripping on internal faults that follow
detection of reverse faults solves the problem.
5-222
operand is asserted by the autorecloser 1.5 cycles after single-pole reclosing is initiated. This
"), then
OPEN POLE OP ΦA
command is present.
setting should be programmed accordingly. If "CBaux OR Custom" is chosen, then the break-
,
, and
BKR ΦB OPEN
BKR ΦC OPEN
GND DIST Z2 PKP
FlexLogic™ operand is the recommended value for this setting. Power system con-
AR DISABLED
L60 Line Phase Comparison System
TRIP 1-POLE INPUT
shall be used for blocking phase A of the instantaneous overcur-
TRIP 1-POLE INPUT-1
settings indicated below. Alternately, a purely custom condi-
FlexLogic™ operand or the
FlexLogic™ operand could be assigned to these
GND DIST Z3 PKP
5 SETTINGS
remains picked-up. The
TRIP 1-POLE
operand
OPEN POLE BLK N
to
values,
TRIP 1-POLE INPUT-6
FlexLogic™
PH DIST Z3 PKP
GE Multilin

Advertisement

Table of Contents

   Also See for GE L60

   Related Manuals for GE L60

Comments to this Manuals

Symbols: 0
Latest comments: