Virtual Outputs - GE L60 Instruction Manual

Line phase comparison system, ur series
Hide thumbs Also See for L60:
Table of Contents

Advertisement

5 SETTINGS
Write the following FlexLogic™ equation (EnerVista UR Setup example shown):
Both timers (Timer 1 and Timer 2) should be set to 20 ms pickup and 0 ms dropout.
Program the Latching Outputs by making the following changes in the
PUTS
CONTACT OUTPUT H1a
"
OUTPUT H1a OPERATE:
VO1
"
"
VO4
OUTPUT H1a RESET:
Application Example 4:
A latching contact H1a is to be controlled from a single virtual output VO1. The contact should stay closed as long as VO1
is high, and should stay opened when VO1 is low. Program the relay as follows.
Write the following FlexLogic™ equation (EnerVista UR Setup example shown):
Program the Latching Outputs by making the following changes in the
PUTS
CONTACT OUTPUT H1a
"
VO1
OUTPUT H1a OPERATE:
"
"
VO2
OUTPUT H1a RESET:

PATH: SETTINGS
INPUTS/OUTPUTS
 VIRTUAL OUTPUT
1
MESSAGE
There are 96 virtual outputs that may be assigned via FlexLogic™. If not assigned, the output will be forced to 'OFF' (Logic
0). An ID may be assigned to each virtual output. Virtual outputs are resolved in each pass through the evaluation of the
FlexLogic™ equations. Any change of state of a virtual output can be logged as an event if programmed to do so.
For example, if Virtual Output 1 is the trip signal from FlexLogic™ and the trip relay is used to signal events, the settings
would be programmed as follows:
GE Multilin
and
menus (assuming an H4L module):
CONTACT OUTPUT H1c
"
OUTPUT H1c OPERATE:
OUTPUT H1c RESET:
menu (assuming an H4L module):
"


VIRTUAL OUTPUTS

VIRTUAL OUTPUT
Virt Op 1
VIRTUAL OUTPUT
EVENTS: Disabled
L60 Line Phase Comparison System

SETTINGS
INPUTS/OUTPUTS
"
"
VO2
"
"
VO3

SETTINGS
INPUTS/OUTPUTS
VIRTUAL OUTPUT 1(96)
Range: Up to 12 alphanumeric characters
1 ID
Range: Disabled, Enabled
1
5.7 INPUTS/OUTPUTS

CONTACT OUT-

CONTACT OUT-
5.7.4 VIRTUAL OUTPUTS