Teleprotection Inputs And Outputs - GE L60 Instruction Manual

Line phase comparison system, ur series
Hide thumbs Also See for L60:
Table of Contents

Advertisement

5 SETTINGS
DIRECT OUT 2 OPERAND:
DIRECT OUT 3 OPERAND:
DIRECT OUT 4 OPERAND:
Signal flow between the three IEDs is shown in the figure below:
UR IED 1
DIRECT OUT 2 = HYB POTT TX1
Figure 5–147: SIGNAL FLOW FOR DIRECT INPUT AND OUTPUT – EXAMPLE 3
In three-terminal applications, both the remote terminals must grant permission to trip. Therefore, at each terminal, direct
inputs 5 and 6 should be ANDed in FlexLogic™ and the resulting operand configured as the permission to trip (
setting).
RX1
a) OVERVIEW
The relay provides sixteen teleprotection inputs on communications channel 1 (numbered 1-1 through 1-16) and sixteen
teleprotection inputs on communications channel 2 (on two-terminals two-channel and three-terminal systems only, num-
bered 2-1 through 2-16). The remote relay connected to channels 1 and 2 of the local relay is programmed by assigning
FlexLogic™ operands to be sent via the selected communications channel. This allows the user to create distributed pro-
tection and control schemes via dedicated communications channels. Some examples are directional comparison pilot
schemes and direct transfer tripping. It should be noted that failures of communications channels will affect teleprotection
functionality. The teleprotection function must be enabled to utilize the inputs.
b) TELEPROTECTION INPUTS

PATH: SETTINGS
INPUTS/OUTPUTS
 TELEPROT INPUTS
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
GE Multilin
"
"
HYB POTT TX1
"
" (forward a message from 1 to 3)
DIRECT INPUT 5
"
" (forward a message from 3 to 1)
DIRECT INPUT 6
DIRECT INPUT 5
DIRECT INPUT 6

TELEPROTECTION
TELEPROT INPUTS
TELEPROT INPUT 1-1
DEFAULT: Off
TELEPROT INPUT 1-2
DEFAULT: Off
TELEPROT INPUT 1-16
DEFAULT: Off
TELEPROT INPUT 2-1
DEFAULT: Off
TELEPROT INPUT 2-2
DEFAULT: Off
TELEPROT INPUT 2-16
DEFAULT: Off
L60 Line Phase Comparison System
UR IED 2
DIRECT INPUT 5
DIRECT OUT 2 = HYB POTT TX1
DIRECT OUT 4 = DIRECT INPUT 6
DIRECT OUT 3 = DIRECT INPUT 5
DIRECT INPUT 6
UR IED 3
DIRECT INPUT 5
DIRECT INPUT 6
DIRECT OUT 2 = HYB POTT TX1

5.7.11 TELEPROTECTION INPUTS AND OUTPUTS

Range: Off, On, Latest/Off, Latest/On
Range: Off, On, Latest/Off, Latest/On
Range: Off, On, Latest/Off, Latest/On
Range: Off, On, Latest/Off, Latest/On
Range: Off, On, Latest/Off, Latest/On
Range: Off, On, Latest/Off, Latest/On
5.7 INPUTS/OUTPUTS
842717A1.CDR
HYB POTT
5-281