5 SETTINGS
The dcmA output settings are described below.
DCMA OUTPUT H1 SOURCE: This setting specifies an internal analog value to drive the analog output. Actual values
(FlexAnalog parameters) such as power, current amplitude, voltage amplitude, power factor, etc. can be configured as
sources driving dcmA outputs. Refer to Appendix A for a complete list of FlexAnalog parameters.
DCMA OUTPUT H1 RANGE: This setting allows selection of the output range. Each dcmA channel may be set inde-
pendently to work with different ranges. The three most commonly used output ranges are available.
DCMA OUTPUT H1 MIN VAL: This setting allows setting the minimum limit for the signal that drives the output. This
setting is used to control the mapping between an internal analog value and the output current. The setting is entered
in per-unit values. The base units are defined in the same manner as the FlexElement™ base units.
DCMA OUTPUT H1 MAX VAL: This setting allows setting the maximum limit for the signal that drives the output. This
setting is used to control the mapping between an internal analog value and the output current. The setting is entered
in per-unit values. The base units are defined in the same manner as the FlexElement™ base units.
The
DCMA OUTPUT H1 MIN VAL
the
DCMA OUTPUT H1 SOURCE
NOTE
Three application examples are described below.
EXAMPLE: POWER MONITORING
A three phase active power on a 13.8 kV system measured via UR-series relay source 1 is to be monitored by the dcmA H1
output of the range of –1 to 1 mA. The following settings are applied on the relay: CT ratio = 1200:5, VT secondary 115, VT
connection is delta, and VT ratio = 120. The nominal current is 800 A primary and the nominal power factor is 0.90. The
power is to be monitored in both importing and exporting directions and allow for 20% overload compared to the nominal.
The nominal three-phase power is:
The three-phase power with 20% overload margin is:
The base unit for power (refer to the FlexElements section in this chapter for additional details) is:
The minimum and maximum power values to be monitored (in pu) are:
minimum power
=
The following settings should be entered:
GE Multilin
I
max
I
min
DRIVING SIGNAL
MIN VAL
Figure 5–149: DCMA OUTPUT CHARACTERISTIC
and
DCMA OUTPUT H1 MAX VAL
is set to FlexAnalog value based on power factor measurement).
P
3
×
13.8 kV 0.8 kA
×
=
×
P
1.2 17.21 MW
=
max
P
115 V 120
×
×
1.2 kA
=
BASE
20.65 MW
------------------------------
1.247 pu,
=
16.56 MW
L60 Line Phase Comparison System
5.8 TRANSDUCER INPUTS AND OUTPUTS
MAX VAL
842739A1.CDR
settings are ignored for power factor base units (i.e. if
×
0.9
17.21 MW
=
20.65 MW
=
16.56 MW
=
20.65 MW
-------------------------- -
maximum power
=
16.56 MW
(EQ 5.34)
(EQ 5.35)
(EQ 5.36)
1.247 pu
(EQ 5.37)
=
5-289