2 PRODUCT DESCRIPTION
2.2SPECIFICATIONSSPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE
The operating times below include the activation time of a trip rated form-A output contact unless otherwise indi-
cated. FlexLogic™ operands of a given element are 4 ms faster. This should be taken into account when using
FlexLogic™ to interconnect with other protection or control elements of the relay, building FlexLogic™ equations, or
NOTE
interfacing with other IEDs or power system devices via communications or different output contacts.
87PC SCHEME
Signal selection:
mixed I_2 – K × I_1 (K = 0.00 to 0.25 in
steps of 0.01), or 3I_0
Angle reference:
0 to 360° leading in steps of 1
Fault detector low:
Mixed signal overcurrent: 0.02 to 15.00 pu in steps of 0.01
I
× Z – V
:
0.005 to 15.000 pu in steps of 0.001
2
2
dI
/ dt:
0.01 to 5.00 pu in steps of 0.01
2
dI
/ dt:
0.01 to 5.00 pu in steps of 0.01
1
I
overcurrent:
0.20 to 5.00 pu in steps of 0.01
1
I
overcurrent:
0.02 to 5.00 pu in steps of 0.01
2
Fault detector high:
Mixed signal overcurrent: 0.10 to 15.00 pu in steps of 0.01
I
× Z – V
:
0.005 to 15.000 pu in steps of 0.001
2
2
dI
/ dt:
0.01 to 5.00 pu in steps of 0.01
2
dI
/ dt:
0.01 to 5.00 pu in steps of 0.01
1
I
overcurrent:
0.50 to 5.00 pu in steps of 0.01
1
I
overcurrent:
0.05 to 5.00 pu in steps of 0.01
2
Signal symmetry
adjustment:
–5.0 to 5.0 ms in steps of 0.1
Channel delay
adjustment:
0.000 to 30.00 ms in steps of 0.001
Channel adjustments:
channel delay and signal symmetry com-
pensation
Operate time (typical):
¾ cycle for single phase comparison
½ cycle for dual phase comparison
Trip security:
first coincidence or enhanced
Second coincidence timer: 10 to 200 ms in steps of 1
Enhanced stability angle: 40 to 180° in steps of 1
Charging current compensation: 0.100 to 65.535 kΩ in steps of
0.001
GE Multilin
PHASE DISTANCE
Characteristic:
Number of zones:
Directionality:
Reach (secondary Ω):
Reach accuracy:
Distance:
Characteristic angle:
Comparator limit angle: 30 to 90° in steps of 1
Directional supervision:
Characteristic angle:
Limit angle:
Right blinder (Quad only):
Reach:
Characteristic angle:
Left Blinder (Quad only):
Reach:
Characteristic angle:
Time delay:
Timing accuracy:
Current supervision:
Level:
Pickup:
Dropout:
Memory duration:
VT location:
CT location:
Voltage supervision pickup (series compensation applications):
Operation time:
Reset time:
L60 Line Phase Comparison System

2.2 SPECIFICATIONS

2.2.1 PROTECTION ELEMENTS

mho (memory polarized or offset) or
quad (memory polarized or non-direc-
tional), selectable individually per zone
3
forward, reverse, or non-directional
0.02 to 500.00 Ω in steps of 0.01
±5% including the effect of CVT tran-
sients up to an SIR of 30
30 to 90° in steps of 1
30 to 90° in steps of 1
30 to 90° in steps of 1
0.02 to 500 Ω in steps of 0.01
60 to 90° in steps of 1
0.02 to 500 Ω in steps of 0.01
60 to 90° in steps of 1
0.000 to 65.535 s in steps of 0.001
±3% or 4 ms, whichever is greater
line-to-line current
0.050 to 30.000 pu in steps of 0.001
97 to 98%
5 to 25 cycles in steps of 1
all delta-wye and wye-delta transformers
all delta-wye and wye-delta transformers
0 to 5.000 pu in steps of 0.001
1 to 1.5 cycles (typical)
1 power cycle (typical)
2