CHAPTER 5: SETTINGS
Application example 4
A latching contact H1a is to be controlled from a single virtual output VO1. The contact is to remain closed as long as VO1
is high, and is to remain opened when VO1 is low. Program the relay as follows.
Write the following FlexLogic equation (EnerVista example shown).
Program the Latching Outputs by making the following changes in the
OUTPUTS  CONTACT OUTPUT H1a
: "VO1"
OUTPUT H1a OPERATE
: "VO2"
OUTPUT H1a RESET

5.8.4 Virtual outputs

SETTINGS  INPUTS/OUTPUTS  VIRTUAL OUTPUTS  VIRTUAL OUTPUT 1(96)
 VIRTUAL OUTPUT 1
The virtual inputs and outputs are digital signals associated with UR-series internal logic signals. Virtual inputs include
signals generated by the local user interface. The virtual outputs are outputs of FlexLogic equations used to customize the
device. Virtual outputs can also serve as virtual inputs to FlexLogic equations.
There are 96 virtual outputs that can be assigned using FlexLogic. If not assigned, the output is forced to 'OFF' (Logic 0). An
ID also can be assigned to each virtual output. Virtual outputs are resolved in each pass through the evaluation of the
FlexLogic equations. Any change of state of a virtual output can be logged as an event if programmed to do so.
For example, if Virtual Output 1 is the trip signal from FlexLogic and the trip relay is used to signal events, the settings is
programmed as follows:
: "Trip"
VIRTUAL OUTPUT 1 ID
VIRTUAL OUTPUT 1 EVENTS

5.8.5 Resetting

SETTINGS  INPUTS/OUTPUTS  RESETTING
 RESETTING
Some events can be programmed to latch the faceplate LED event indicators, target messages, and/or graphical panel
annunciator windows. Once set, the latching mechanism holds all of the latched indicators or messages in the set state
after the initiating condition has cleared until a
latches) to the reset state where the initiating condition has cleared. The
button, a remote device via a communications channel, or any selected operand.
RESET
B90 LOW IMPEDANCE BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
menu (assuming an H4L module):
VIRTUAL OUTPUT 1 ID
Virt Op 1
VIRTUAL OUTPUT 1
EVENTS: Disabled
: "Disabled"
RESET OPERAND:
Off
command is received to return these latches (not including FlexLogic
RESET
SETTINGS  INPUTS/OUTPUTS  CONTACT
Range: up to 20 alphanumeric characters
Range: Disabled, Enabled
Range: FlexLogic operand
command can be sent from the faceplate
RESET
INPUTS/OUTPUTS
5
5-179