4.3.3. Digital inputs and outputs

External 24 V supply
Caution!
GND is internally connected to PE
via jumper BR-PE.
+Vcc
G N D
20 21 22 24 26 27 28 39 40 41 42 44 59
Legend
Marking
Digital outputs
RDY
I 7 50mA
Qmin
TRIP
Digital inputs
RFR
(active at 13 ... 30 V)
TRIP RESET
I 7 10mA
TRIP SET
JOG
QSP
?
Relay
@

Internal 15 V supply
+Vcc
X5
20 21 22 24 26 27 28 39 40 41 42 44 59
?
-
+
Function at signal = HIGH
Ready
Motor speed > value of C017 (factory Setting)
The function depends on C117
No faults
Controller enable
Fault reset
No fault switch-off (Motor thermostat)
Internal set value
No quick stop with this switch position
≥ 1 kΩ,
Relay 24 V, R
i
≥ 600 Ω,
Relay 15 V, R
i
Caution!
Bridge signals X5,39 and X5,40.
G N D
e.g. order no. EK00326005
e.g. order no. EK00326850
X5
@