4
Technical data
StateLine C control terminals
Digital inputs
4.6.4
Digital inputs
Labelling
X4/DI1, DI2
X4/DI3, DI4
X4/RFR
X4/GIO
4.6.5
Digital outputs
Labelling
X4/DO1
X4/GIO
4.6.6
Relay output connection
Labelling
X101
COM
NC
COM
NO
COM
56
efesotomasyon.com - Lenze
Features
Digital input 1/2
Digital input 3/4
Controller inhibit
Input resistance
Electric strength of external voltage
Isolation
Level
Cycle time
GND, reference potential for digital signals
Features
Digital output
External−voltage protected
Isolation
Level
Time−dependent behaviour
Overload behaviour
Reset and switch−on behaviour
Cycle time
GND, reference potential for digital signals
Description/features
Central contact of relay
NC contact (normally closed)
Position is displayed via TRIP software
message
(Lenze setting)
NO contact (normally open)
l
Rated value
In accordance with IEC61131−2, type 1
or
two−track frequency input for HTL
encoder 0 ... 10 kHz
In accordance with IEC61131−2, type 1
In accordance with IEC61131−2, type 1
3.3 kW (2.5 kW ... 6 kW)
Up to ±30 V, permanent
^ 85
LOW < +5V
HIGH > +15V
1 ms, can be changed by software
filtering
Rated value
In accordance with IEC61131−2, type 1, max.
50 mA
Up to +30 V
Integrated polarity reversal protection diode
for switching inductive loads
^ 85
LOW < +5 V
High > +15 V
LOW − HIGH / HIGH − LOW
Max. 250 ms
Reduced voltage or periodical switch−off/on
Outputs are switched off (LOW)
1 ms
Rated value
AC 250 V, 3 A
DC 24V, 2A
DC 240 V, 0.16 A
l
According to UL508C:
– 3 A, 250 V AC (general purpose)
– 2 A, 24 V DC (resistive)
– 0.16 A, 240 V DC (general purpose)
EDS84ASC552 EN 6.0