Resetting The Safety Function Parameters To The Factory Setting - Siemens SINAMICS G120 Function Manual

Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

5.4

Resetting the safety function parameters to the factory setting

Procedure
To reset the safety function settings to the factory setting without changing the standard
settings, proceed as follows:
1. Go online with STARTER
2. Open the screen form for the safety functions
3. Press the button to restore the factory settings
4. Enter the password,for the safety functions.
5. Confirm saving parameters (RAM to ROM).
6. Go offline with STARTER .
7. Switch off the inverter supply voltage.
8. Wait until all LED on the inverter go dark. Now switch on the inverter supply voltage again
You have restored the safety functions in the inverter to the factory settings.
Parameters Description
p0010
p9761
p9762
p9763
p0970
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 04/2014, FW V4.7, A5E34261271B AA
(power on reset).
Drive, commissioning parameter filter
0
Ready
30
Parameter reset
Enter a password (factory setting: 0000 hex)
Permissible passwords lie in the range 1 ... FFFF FFFF.
New password
Password confirmation
Confirming the new Safety Integrated password.
Reset drive parameters
5
Starts a safety parameter reset.
After the reset, the inverter sets p0970 = 0.
5.4 Resetting the safety function parameters to the factory setting
.
.
Commissioning
85

Hide quick links:

Advertisement

Table of Contents