5.18 No Output before PASS Range

Comparative set value HH/H
Comparative set value LL/L
f
stdby
L
(STDBY)
0
L
Displays "L 0."
amov
0
L
0
amov
0
L
00000
init
f
L
off
Displays "L f."
The standby sequence function can be used to prevent outputs from
turning ON for unstable inputs after the power is turned ON. All outputs
will remain OFF until the measurement value reaches the PASS value.
Output PASS
Output LL/L
All outputs will remain OFF after power is turned ON
until the measurement value reaches the PASS value.
Parameter
Standby sequence
stdby
Parameter Setting Procedure
A Press the L [LEVEL] Key for at least 3 s in RUN level to move to
L
the initial setting level.
3 s min.
0" is displayed on the level/bank display to indicate the initial
• "
L
setting level.
B Press the M [MODE] Key several times to change the PV display
M
to "amov."
• This parameter is not displayed for the initial status due to
setting level protect.
Refer to "5.34 Limiting Key Operations" (P.5-84) for information
on removing setting level protect.
C Press the S [SHIFT] Key to make the SV display flash.
S
• The setting can be changed when the SV display starts to
flash.
D Use the U [UP] and S [SHIFT] Keys to set the password "-
U
0169." Press the M [MODE] Key to move to the advanced
function setting level.
M
f" is displayed on the level/bank display to indicate the
• "
L
advanced function setting level.
5.18 No Output before PASS Range
Advanced function setting level
Measurement value
Set value
Meaning of set value
off
Disabled
on
Enabled
R
P
ON
OFF
5-55