Hardware Configuration Of The Sitop Ups Module - Siemens SINUMERIK MC Commissioning Manual

Mcu commissioning: nc, plc, drive
Hide thumbs Also See for SINUMERIK MC:
Table of Contents

Advertisement

Procedure
1. Call the SITOP UPS Manager.
2. Change to "Software configuration > Buffer mode".
3. Make the following settings:
– Activate the checkbox "Start application on power failure" - and there, enter the path of
– When required, configure the wait time until the HMI software is terminated by
4. Confirm the settings with "Configuration changed, restart application now".
10.3.12.4

Hardware configuration of the SITOP UPS module

Buffering parameterization
The UPS module can be used to select whether buffering should be completed after a
predetermined period of time or not until the accumulator's lowest discharge threshold (=
maximum buffer time) has been reached. Both buffering parameterizations result from this.
"Maximum buffer time" mode
This mode enables the system to be shut down in a time-optimized manner. The UPS module
is synchronized with the shutdown of the operating system. Buffering is maintained until the
operating system has been shut down. The operating system must shut down within a
maximum of 5 minutes (including all applications). Otherwise, the UPS module buffers for the
maximum buffer time (dependent on the accumulator state).
Required settings on the UPS module (USB interface)
MCU commissioning: NC, PLC, Drive
Commissioning Manual, 02/2020, A5E47437618B AB
USVShutdown.bat:
C:\Program Files (x86)\Siemens\MotionControl\siemens\sinumerik\hmi\base
\USVShutdown.bat
USVShutdown.bat (factory setting = 180 seconds).
Note
Information about the test environment for machine OEMs
The function "SITOP UPS" has been tested in the standard configuration with
PCU Base for IPC. When installing add-on or OEM software components, you must
check the shutdown procedure of the entire system and adapt the factory setting.
To do this, enter the wait time in seconds as command line parameter:
Syntax: <path>\USVShutdown.bat -<time in seconds>
Example: C:\Program Files (x86)\Siemens\MotionControl\siemens\sinumerik\hmi\base
\USVShutdown.bat -180
On - Off
1
+2V
2
+1V
3
+0.5V
Installing and setting up PCU Base for IPC
10.3 Configuration of the system
Cut-in threshold
+22V fixed
197