Siemens SINUMERIK MC Commissioning Manual page 132

Mcu commissioning: nc, plc, drive
Hide thumbs Also See for SINUMERIK MC:
Table of Contents

Advertisement

Commissioning NC-controlled drives
6.3 Commissioning drives via device master files
Procedure
1. Under "Project navigation > Ungrouped devices", double-click the drive you created.
The device configuration for the drive is displayed in the Inspector window.
2. In the Inspector window under "Properties > General > PROFINET interface [X150] >
Ethernet addresses", in the "IP Protocol" screen section set the IP address of the drive.
3. In the "PROFINET" screen section, activate "Automatically generated PROFINET device
name".
132
MCU commissioning: NC, PLC, Drive
Commissioning Manual, 02/2020, A5E47437618B AB