Installing and setting up PCU Base for IPC
10.5 Backing up and restoring data
Preconditions
The following conditions must be met in order to use this function:
● The PG is connected to NC interface X127 in the system network.
● NC and IPC are connected via the system network.
● On the NC the routing is activated in one of the following ways:
– In SINUMERIK Commissioning, the routing is configured in the user interface "System
– In the configuration file basesys.ini, key EnableSysNetToIBNForwarding=1 is set.
● If you wish to access a network directory, it must be shared.
● The user account in question is known to the PG/PC.
● The Service Center is active.
Procedure
To configure the IP routing in the Service Center, proceed as follows:
1. In the main menu of the Service Center, click "Network".
2. In the "Network Settings" dialog box, click the "IP Routing" tab.
Figure 10-19
3. Configure the necessary routes.
Further information: Network settings in the Service Center (Page 247)
264
network settings".
Service Center - IP routing
MCU commissioning: NC, PLC, Drive
Commissioning Manual, 02/2020, A5E47437618B AB