Cancelling a parallel connection
You can cancel an existing parallel connection as follows:
1. Drag components to the higher-level drive unit using drag-and-drop.
- Or -
2. Select a component connected in parallel and select the "Disconnect parallel connection"
shortcut menu.
Creating the configuration
After you have checked and, if required, corrected the topology determined in the configuration,
you can transfer this topology to a Startdrive project.
1. Make sure that there are no non-assignable components in the "Device configuration
detection" dialog.
Only when there are no non-assignable components is the "Create" button active.
2. Click the "Create" button.
The components are created in the offline condition. While the topology is being created, an
interruptible progress dialog is displayed. If you interrupt the operation, the online connection
is maintained. After creation, the topology is displayed in the device view.
Result
The topology is created in the device configuration of the selected drive unit. The view changes
into the device view.
The online connection with the target device is automatically disconnected. As a consequence,
you can immediately make changes to the specification or configuration of the components.
This would not be possible in the online mode.
MCU commissioning: NC, PLC, Drive
Commissioning Manual, 02/2020, A5E47437618B AB
Commissioning NC-controlled drives
6.2 Commissioning drives with "Startdrive"