Commissioning NC-controlled drives
6.2 Commissioning drives with "Startdrive"
Port interconnection via the properties
After the selection of a device or an interface, the entries for the ports are displayed in the
Inspector window in the "General" tab at "PROFINET PN / IO interface > Advanced options" or
"Advanced options".
1. Select the interface, whose ports you want to edit, from the Inspector window.
2. Select the interface you wish to interconnect.
3. Select the "Port interconnection" entry.
The "Local port" and "Partner port" dialogs open.
4. Open the "Partner port" drop-down menu.
All devices with their PROFINET interfaces are shown.
5. Below the respective interface, select the port you want to connect to the selected port.
Ports that you cannot connect are marked in red. Ports that are already assigned are not
displayed.
The connection between the ports is displayed in the topology view.
6. If necessary, edit the other parameters of the port.
114
MCU commissioning: NC, PLC, Drive
Commissioning Manual, 02/2020, A5E47437618B AB