Output Frequency Limit; Dc Injection Braking - Omron SYSDRIVE 3G3XV-EV2 Series Operation Manual

Table of Contents

Advertisement

Description of Functions and Constants

2-8-10 Output Frequency Limit

Item name
Frequency (speed) command upper limit
Frequency (speed) command lower limit
Note

2-8-11 DC Injection Braking

Item name
DC injection braking current
DC injection during stop
DC injection at start
DC Injection Braking
Current
DC Injection Braking
During Stop
Starting DC Injection
Braking During Start
50
Constant to be set
No. 24
No. 25
The upper and lower limits for the output frequency can be
clamped. When the lower limit is not 0, acceleration to that lower
limit setpoint begins immediately when the start command is input.
Output frequency
100%
No. 24
No. 25
0
100%
Frequency command
By setting constant No. 24 to 110%, frequencies up to 1.1 times the
value of constant No. 2 can be output. However, 400 Hz is the high-
est frequency that can be output.
For example, assume constant No. 2 = 60 Hz. A frequency of 66 Hz
will be output if constant No. 24 = 1.1.
Constant to be set
No. 26
No. 27
No. 28
A 100% setting for the DC injection braking current equals the
Inverter's rated current. The default setting set at the factory prior
to shipping is 50%.
Prevents overrun at stop. (Exact position stop)
Frequency
No. 7
Current
No. 26
No. 27
Stops a coasting motor without tripping even when the direction of
rotation is unknown.
Frequency
No. 7
Current
No. 26
No. 28
100%
0
50%
0.5 s
0.0 s
Time
Time
Time
Time
Section 2-8
Factory preset
Factory preset