Installation Site Size Requirements; Minimum Required Free Space For Operation And Maintenance - AGFA CR Series Service Manual

Digitizer
Table of Contents

Advertisement

DD+DIS170.11E
3

Installation Site Size Requirements

3.1

Minimum required free Space for Operation and Maintenance

The footprint of the digitizer is
42 cm (width) x 32 cm (depth). See
also NOTE below.
To have a safety margin of 10 cm at
each side a table size of minimum
62 cm (width) x 52 cm (depth) is
required.
When placing the table at the wall
with the rear side, the minimum
table depth is 52 cm.
For operation a free space of
minimum 62 cm x 80 cm in front of
the digitizer is recommended.
For corrective maintenance the
digitizer can be carried to a place
with sufficient space if required.
NOTE:
Figure 5 shows the footprint of the
digitizer.
The controlled version of this document is available from the Agfa HealthCare Library. Any printed copy of this document is uncontrolled.
Edition 1, Revision 1
03-2013
DOCUMENT CONTROL NOTE:
CR 10-X / CR Reader / CR 12-X / CR Advanced Reader Chapter 11 / Page 10 of 24
Type 5151 / 100 / 110 / 200 / 210
Installation Planning
Figure 4
Front
Bottom view
32 cm [12,6 in.]
Figure 5
Agfa Company Confidential