Mains Signaling Voltage; Memory Management - Siemens SICAM Q100 7KG95 Series Manual

Class a power quality instrument and power monitoring device
Hide thumbs Also See for SICAM Q100 7KG95 Series:
Table of Contents

Advertisement

Tolerance unit
Tolerance number
Maximum recording interval
16.5.4

Mains Signaling Voltage

Parameter
MSV active
No. of MSV frequencies
Frequency 1
Frequency 2
Detection threshold
Total recording duration
Pretrigger ratio
16.5.5

Memory Management

Parameter
Event recorder
Measurement recorder
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
Percentage
Percentage: 3 % of primary
nominal voltage,
Numerical: 0.50 V
10 min
Default Setting
Mains signaling voltage measurement
no
1 frequency
216.60 Hz
1060.00 Hz
Mains signaling voltage capture setting
1 % of Udin
75 s
10 %
Default Setting
Memory splitting
1.0 %
35.0 %
(the recording time depends on
the aggregation interval)
16 Operating Parameters
16.5 Recording and Reporting
Percentage
Numerical
1 % to 5 % in 1-% steps
0.2 V to 500.0 V
10 min, 30 min,
1 h, 2 h, 4 h, 6 h, 12 h, 24 h
Setting Range
no
yes
1 frequency
2 frequencies
100 Hz to 3 kHz
100 Hz to 3 kHz
From 1 % to 15 % of Udin
15 s to 120 s in 15-s steps
0 % to 30 % in 5-% steps
Setting Range
1 % to 19 %
33 % to 51 %
415

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents