9 Operation at Use of a PC
9.3 Configuration of the Device
Table 9-26
Column
Threshold [%]
Zero-point [Unit]
Aggregate [0,1]
1)
The threshold value in unit depends on the last value transmitted to the MQTT broker.
2)
If the last transmitted value is 0, a measured-value change is transmitted immediately with a fixed zero-
point suppression value.
Table 9-27
Operational and harmonic values
10/12 cycle RMS values
Aggregated values
Minimum values
Maximum values
Frequency
Aggregated values
Minimum values
Maximum values
Threshold
For the transmission of 10/12 cycle RMS values and harmonics, a threshold processing is executed based on
the following thresholds and method:
The thresholds related to the last transmitted value
A combined fixed and integrated threshold method
230
Columns in the Mapping File
Value
Point value
2)
Point value
0
1
Prefixes of the Names for Different Values
Value Type
Description
The threshold value in percentage
Only available for non-aggregated values
Zero-point suppression value in unit
Only available for non-aggregated values
0 = 10/12 cycle RMS values
1 = aggregated values
This column shows whether the data point is published as
aggregated values or as 10/12 cycle RMS values with
threshold processing.
PQA0
PQA2
MIN_PQA2
MAX_PQA2
PQA4
MIN_PQA2
MAX_PQA2
E50417-H1040-C522-A6, Edition 06.2019
1)
Prefix
SICAM Q100, 7KG95xx, Device Manual