9.7.3
Parameterization as Defined by the Task
Requirements
SICAM Q100 is electrically connected to the system and commissioned as described in chapter 7.7. Rated
voltages and currents at the measuring inputs are switched off.
Parameterization
NOTE
If you change settings in tabs, click Send on each tab to confirm the new setting. The settings are activated
only after the entire parameterization has been completed.
✧
Start the user interface as described in chapter 9.2.1 (initial startup) or chapter 9.2.7 (start during
operation). Use the factory-preset IP address for this purpose.
✧
On the Configure tab, configure the element AC measurement (see chapter 9.3.3.1.1) according to the
following topology specifications:
Figure 9-142
NOTE
If you are using Ethernet communication with IEC 61850 bus protocol (chapter 9.3.7.2) and change the
Network type, the device will restart.
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
Configure Tab, AC Measurement Example
9.7 Example of a Parameterization and Measured Value Evaluation
9 Operation at Use of a PC
329