9.3.7.2.1
Parameterizing the Ethernet Communication with Modbus TCP Bus Protocol
General Settings Communication Ethernet
To change the Ethernet communication settings, proceed as follows:
In the navigation window, click the Administrative menu and then the element Communication
Ethernet. Select the bus protocol Modbus TCP.
Figure 9-57
Enter the desired values in the fields and select the parameters in the list boxes and in the option field as
described in Table
NOTE
The enabling of SNMP via option Enable SNMP is only required if you want to save the SICAM Q.mib file and
use it in a MIB browser. See also section If you do not want to make any additional settings, continue with
the Activation of the device configuration according to section Activating the Set of Parameters. If you
want to change other settings, enter the changes and then enable the device configuration as descri-
bed in section Activating the Set of Parameters..
NOTE
After changing the network settings and subsequent parameter activation the device will reset.
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
Configure Tab, Communication Ethernet via Modbus TCP Input/Output Window
9-24.
9 Operation at Use of a PC
9.3 Configuration of the Device
217