9.3.6.4 Mains Signaling Voltage
Default Settings and Setting Ranges
Table 9-18
Parameter
MSV active
No. of MSV frequencies
Frequency 1
Frequency 2
Detection threshold
Total recording duration
Pretrigger ratio
Changing the Mains Signaling Voltage Parameters
To change the Mains signaling voltage, proceed as follows:
In the navigation window, select the Recording and Reporting menu and click Mains signaling voltage.
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
Mains Signaling Voltage
Default Setting
Mains signaling voltage measurement
no
1 frequency
216.60 Hz
1060.00 Hz
Mains signaling voltage capture setting
1 [% of Udin]
75 s
10 %
9 Operation at Use of a PC
9.3 Configuration of the Device
Setting Range
no
yes
1 frequency
2 frequencies
100 Hz to 3 kHz
100 Hz to 3 kHz
1 % to 15 % of Udin
15 s to 120 s in 15-s steps
0 % to 30 % in 5-% steps
203