After recording has started, the Recording status fields shows the entry Running.
If you want to stop the recording, click on Stop recording and execute the activation.
The Recording status field shows the entry Not running and Start recording is displayed on the user
interface.
NOTE
The restart of the record is carried out after a power failure automatically.
The status will change from Not running to Running when user change and activate parameters.
Recording Power Quality Data
When the device is started for the first time, it is necessary for the recording of power quality data that the Time
synchronization of the device is set to the current time first. If the time is incorrect, the power quality measure-
ments do not conform to the current time. Proceed as follows:
Refresh the time via Ethernet NTP or Field bus in line with chapter 9.3.7.1 or with the device-internal
clock in line with chapter 9.5.3.2.
Configure all necessary parameters (for example, AC measurement, Communication) on the relevant
tabs, except for the Recording parameters settings.
When setting the parameters, make sure that the settings are consistent with each other (for example,
setting of the flicker lamp model consistent with the primary nominal voltage).
At last, parameterize the Recording parameters and activate the settings.
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
9 Operation at Use of a PC
9.3 Configuration of the Device
211