9.3

Configuration of the Device

NOTE
The device contains two sets of parameters. The set of parameters currently used for device operations is the
active set of parameters. The inactive set of parameters is called the passive set of parameters.
The following sections describe how to change and enable the passive set of parameters.
9.3.1

Device Configuration Procedure

If you have not changed the set of parameters since the first start of the device (see chapter 9.2.1), use the
factory settings (see chapter 9.3.3 to chapter 9.3.7). To change the settings of the set of parameters, proceed
as follows:
Click the Configure tab on the user interface.
Figure 9-14
Select the Prepare menu in the navigation window and then either Get device configuration or Open
configuration from file.
NOTE
If you have selected Get device configuration, an editable copy of the active parameter set of the device is
displayed on the screen. In the meantime, the active parameter set in the device continues to operate.
If you have selected Open configuration from file, you can open and enable or edit the copy of a parameter
set that was already created and saved to a folder.
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
Configure Tab
9 Operation at Use of a PC
9.3 Configuration of the Device