Connect the cables of the supply voltage on the terminal side of the device at terminal block H as follows:
Supply from the Alternating Voltage System
Terminal N/-:
Terminal L/+:
Terminal
Supply from a Direct Voltage Source
Terminal N/-:
Terminal L/+:
Terminal
NOTE
Always connect the grounding at the SICAM Q100 to the terminal for the protective conductor
(terminal block H).
Terminals
Terminals for supply voltage (H), inputs for current measurement (E), inputs for voltage measurement (F), bi-
nary inputs (U) and binary outputs (G) on the terminal side:
Conductor cross-section, rigid max.
Conductor cross-section (conductor with ferrule)
Conductor cross-section (conductor with ferrule, terminal F)
Tightening torque
RS485 interface (J) on the terminal side:
Ethernet interface (Z) on the top side:
Voltage measuring inputs: In the case of a direct connection and transformer connection, the device has
to be safeguarded with a listed 10 A backup fuse or a listed 10 A miniature circuit breaker. When using voltage
transformers, their secondary connections must never be short-circuited!
7.4

System Requirements

To operate SICAM Q100 with a PC or notebook, the following system requirements must be met:
PC or notebook with Intel processor (or compatible type); clock frequency min. 800 MHz
Operating system: Microsoft Windows XP Professional, Windows 7, and Windows 10 with Internet Explor-
er 9.0 (or higher) or Firefox
Minimum 1 GB RAM primary storage
VGA display 1024 x 768 with truecolor
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
Neutral conductor of the supply voltage
Phase of the supply voltage
:
Protective grounding terminal
Negative supply voltage
Positive supply voltage
:
Protective grounding terminal
7.4 System Requirements
2.5 mm² (AWG 14)
1.5 mm² (AWG 16)
2.5 mm² (AWG 14)
0.4 Nm to 0.5 Nm (3.5 in-lb to 4.5 in-lb)
RS485 cable with 9-pole D-sub socket
Ethernet patch cable or crossover cable
7 Getting Started
119