9 Operation at Use of a PC
9.3 Configuration of the Device
Table 9-16Recorder Parameter
Tolerance unit
Tolerance number
Maximum recording interval
1)
The interval of aggregated values of harmonics and interharmonics will always synchronize with the setting
of Average interval in Measurement recorder.
Parameterizing the Recorder Parameters
To change the Recorder management, proceed as follows:
In the navigation window, select the Recording and Reporting menu and click Recorder management.
Figure 9-48
Select the desired parameters in the list boxes and option fields as described in Table 9-16.
NOTE
The voltage is recorded in the following connection types:
3P4W (3 phases/4 wires): phase-to-phase voltage or phase-to-ground voltage
3P3W (3 phases/3 wires): only phase-to-phase voltage
After the parameterization click Send.
The parameters are transmitted to the device but not enabled yet (passive set of parameters).
198
Percentage
Percentage: 3 % of primary
nominal voltage,
Numerical: 0.5 V
10 min
Configure Tab, Recorder Management Input/Output Window
Percentage
Numerical
1 % to 5 % in 1-% steps
0.2 V to 500.0 V
10 min, 30 min,
1 h, 2 h, 4 h, 6 h, 12 h, 24 h
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019