Advertisement

16.5.6

Report Configuration

Company:
Department:
Supervisor:
Inspector:
Location:
Comment:
Evaluation mode according to:
Flagging acc. to
IEC 61000-4-30
Power frequency:
99.5 % of measurement should be in -1.0 % to 1.0 % deviation of the
power frequency.
100 % of measurement should be in -6.0 % to 4.0 % deviation of the
power frequency.
Power supply voltage magnitude
95 % of measurement should be in -10.0 % to 10.0 % deviation of the
nominal/declared supply voltage.
100 % of measurement should be in -15.0 % to 10.0 % deviation of the
nominal/declared supply voltage.
Voltage unbalance:
95 % of measurement should be less than 2.0 %.
100 % of measurement should be less than 3.0 %.
Subgroup Total Harmonic Distortion (THDS):
95 % of measurement should be less than 8.0 %.
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
Parameter
1)
Default Setting
General Information
-
Power Quality Report
EN 50160 LV&MV
no
16 Operating Parameters
16.5 Recording and Reporting
Setting Range
Any text displayed in the print-
out of the power quality report
EN 50160 LV&MV
EN 50160 HV
User defined
no
yes
Any setting for user-defined
evaluation mode
Any setting for user-defined
evaluation mode
Any setting for user-defined
evaluation mode
Any setting for user-defined
evaluation mode