Advertisement

Indication
Limit Violation x
Indication 1 from
Remote
Indication 2 from
Remote
Indication x from
Remote
Binary Input 1
Binary Input 2
Rotating Field Clock-
wise
Group indication x
Voltage Event Availa-
ble
Frequency Event
Available
Volt. Unbalance
Event Available
SD Card Error
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
Description
Indication that a parameterized lim-
iting value has been violated
Status of the indications that can be
set to control the LEDs and the
binary outputs via the communica-
tion.
Status of any indications which can
be set for control via communica-
tion.
Indication of the logic state of the
binary input (ON/OFF)
Indication of rotation voltage
Up to 4 single-point indications can
be linked logically and combined to
a group indication.
Indication of a supply voltage event
Indication of a frequency event
Indication of a voltage unbalance
event
Indication of an SD card error
Notes
Indication on: The limit of the monitored measured value
has been violated or no measured value is parameter-
ized as input of the limiting value.
Indication off: The limit of the monitored measured value
is not violated.
Message invalid: The monitored measured value is
invalid
(e.g. frequency at V < 15 % of V
x = 1 to 16
Indication on: ON
Indication off: OFF
Message invalid: Not yet updated via the communication
or again invalid via the communication
Indication on: ON
Indication off: OFF
Message invalid: Not yet updated via the communication
or again invalid via the communication
x = 3 to 14
Indication invalid: in startup not updated
Binary input high: ON (OFF if inverted)
Binary input low: OFF (ON if inverted)
If the binary input has not been set to a function (load
profile, tariff TOU), a change is logged as an operational
indication; otherwise not, according to factory setting
(can be set).
Indication ON: Phase sequence Va-Vb-Vc, rotation
clockwise
Indication OFF: Phase sequence Va-Vc-Vb, (2 phases
interchanged); rotation anti-clockwise
Indication invalid: Direction of rotation cannot be calcu-
lated (e.g. no voltage applied)
A total of 4 group indications (x = 1 to 4) can be param-
eterized.
Overvoltage, undervoltage, frequency interruption
Overfrequency or underfrequency
Voltage unbalance
SD card defective or read/write error
15 Operational Indications
).
rated
1)
395