15 Operational Indications
Indication
Ethernet Link Error
Modbus TCP OK
(Modbus TCP Server)
Modbus RTU Master
OK
IEC 61850 Communi-
cation OK
MQTT Communica-
tion OK
Settings Load
Settings Check
Settings Activate
394
Description
Ethernet connection error
At least one Modbus TCP link has
received Modbus messages.
All configured Modbus slave
devices respond to request tele-
grams.
Communication via protocol
IEC 61850 is correct.
The communication to an MQTT
broker is successfully established.
Starting to change the parameters
of the passive set of parameters.
The passive set of parameters is to
be activated; the internal parame-
ter check is running.
The passive set of parameters is
enabled and the device works with
these parameters.
Notes
Indication on: Error
Indication off: Ethernet link recognized
Indication on: At least one Modbus message was re-
ceived during the set monitoring time. The time stamp is
set when the first valid message is received.
Indication off: No Modbus message was received during
the set monitoring time.
See chapter 9.3.7.2
Indication on: If all configured Modbus slave devices
respond successfully to request telegrams.
Indication off: If at least one Modbus slave device does
not respond to a request telegram or if at least one
Modbus slave device responds with a Modbus exception
code (see System Manual Q100; chapter 2.2.2).
See chapter 9.3.7.3
Indication on: At least one message was received during
the set monitoring time. The time stamp is set when the
first valid message is received.
Indication off: No message was received during the set
monitoring time.
See chapter 9.3.7.2
Indication ON: The communication to an MQTT broker
is successfully established.
Indication OFF: The communication to an MQTT broker
is not established.
Indication on: Start of changes
Indication off: Changes complete
Indication on: Check started
Indication off: Check complete
Indication on: Activation started
Indication off: Activation complete
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019