Siemens SICAM Q100 7KG95 Series Manual page 176

Class a power quality instrument and power monitoring device
Hide thumbs Also See for SICAM Q100 7KG95 Series:
Table of Contents

Advertisement

9 Operation at Use of a PC
9.3 Configuration of the Device
Parameterizing a Limit
To change, for example, limit 1, proceed as follows:
In the navigation window, select the Operational parameters menu, then the Select automation
functions submenu and click Limits 1-8.
Figure 9-33
Enter the desired values in the fields and select the parameters in the list boxes and option fields as
described in Table 9-6.
Hysteresis of the Limit Value Violation
100 %
Limit Max
Limit Min
0 %
Figure 9-34
NOTE
Select Measurement -none- to disable the corresponding limit indication.
176
Configure Tab, Limits 1-8 Input/Output Window (Detail)
Permissible
Start
End
Start
Hysteresis (General Representation)
Hysteresis range
range
t
End
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019