6.5

TCP/UDP Ports Used

The following table contains an overview of the TCP/UDP ports used.
Table 6-10
Communication
Protocol
HTTPS
NTP
Modbus TCP
Modbus TCP
IEC 61850
DHCP
Syslog
NOTE
One port cannot be assigned to more than one function at the same time.
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
Overview
Server/
TCP/
Client
UDP
Server
TCP
Client
UDP
Server
TCP
Server
TCP
Server
TCP
Client
UDP
Client
UDP
Port
Activated
by Default
443
Yes
123
No
502
Yes
10 000 to
No
65 535
102
No
68
No
514
No
6 Security
6.5 TCP/UDP Ports Used
Description
TLS connection to a Web
browser for device configuration
and value view
Time synchronization
Communication with a station
controller using Modbus TCP
and Modbus default TCP port
Port number is configurable in
the given range. Communication
with a station controller using
Modbus TCP and a user-defined
TCP port
Communication with a station
controller using IEC 61850
Dynamic Host Configuration
Protocol
Syslog protocol