Table 9-37
Label
ML
MV
9.3.7.5.5
Mapping – Import
Click the button Import.
Figure 9-77
Click Browse....
The File Download dialog opens.
Select the desired file (extension .txt) in the directory.
In the tab, click Open.
The information of the text file is applied by SICAM Q100 and interpreted in the passive parameter set. In
the case of faulty data, an error message is entered in the error log, see chapter 9.2.7.3.
NOTE
If you have activated the option in your web browser to transfer the local directory name together with the file
name when uploading files, then the total number of characters in the directory and file names may not exceed
100 english characters. Otherwise, the .txt file in your device will not be updated.
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
Description and setting ranges of the parameters in the text file.
Measured
Quantity (MV)
Indication (I)
Factor (Unit multiplier) for measu-
ring value
Import
Description
9 Operation at Use of a PC
9.3 Configuration of the Device
Setting Range
-3: milli (m)
-2: centi (c)
-1: deci (d)
0: no multiplier
2: hecto (h)
3: kilo (k)
6: Mega (M)
9: Giga (G)
251