Siemens SICAM Q100 7KG95 Series Manual page 252

Class a power quality instrument and power monitoring device
Hide thumbs Also See for SICAM Q100 7KG95 Series:
Table of Contents

Advertisement

9 Operation at Use of a PC
9.3 Configuration of the Device
9.3.7.6 SICAM Subdevices
The internal Ethernet switch and a Y cable or an external Ethernet switch can be used to connect up to 2 sub-
devices of the type SICAM I/O Unit 7XV5673 to SICAM Q100. The communication takes place with the Modbus
UDP protocol. For further information and connection examples, refer to the System Manual SICAM Q100,
chapter 2.
9.3.7.6.1
SICAM Subdevice – Parameterization in SICAM Q100
Default Settings and Settings of the SICAM Subdevices
Table 9-38
Parameter/Indications
Subdevice 1
Subdevice 2
Subdevice 1
Server IP address
Server port
Response timeout
Parameter: Source of output 1-N
Indication: Input 1-N
Parameter: Source of output 2-N
Indication: Input 2-N
Parameter: Source of output 3-N
Indication: Input 3-N
Parameter: Source of output 1-P
Indication: Input 1-P
Parameter: Source of output 2-P
Indication: Input 2-P
Parameter: Source of output 3-P
Indication: Input 3-P
Subdevice 2
252
Settings of the SICAM Subdevices
-none-
No further indications are
displayed.
192.168.0.56
51 000
3 (* 10 ms)
Indication 3 from Remote
Binary inp. 1-N SICAM IO 1
Indication 4 from Remote
Binary inp. 2-N SICAM IO 1
Indication 5 from Remote
Binary inp. 3-N SICAM IO 1
Indication 6 from Remote
Binary inp. 1-P SICAM IO 1
Indication 7 from Remote
Binary inp. 2-P SICAM IO 1
Indication 8 from Remote
Binary inp. 3-P SICAM IO 1
Default Setting
-none-
SICAM IO
any
(different from IP address of subde-
vice 2 and in the same subnet as
SICAM Q100)
10 000 to 65 535
10 ms to 60 000 ms
0 ms = invalid
Parameter: see chapter 16
Indication: any, max. 31 characters
Parameter Source of output:
Selection which indication is trans-
mitted from SICAM Q100 to the
binary output of the SICAM I/O Unit
7XV5673.
Indication Input:
Designation of the indication which
shows the status of the binary input
of SICAM I/O Unit 7XV5673.