9 Operation at Use of a PC
9.3 Configuration of the Device
Table 9-24
Activated
Unit ID of this device
3)
Retry limit
Response timeout
IED Name
Voltage - Dead band
Current - Dead band
Power - Dead band
Power factor - Dead band
Frequency - Dead band
1)
After the parameter changes have been enabled, the device will reset.
2)
After enabling the parameter changes, any currently active Modbus TCP connections will be closed. The
Modbus TCP client must later reopen these connections.
3)
These values are necessary if no Modbus slave device has been configured for the requested Unit ID. If a
Modbus slave device was configured, its values are used.
216
Communication Ethernet Settings (cont.)
Parameter
3)
Default Setting
no
255
2
10 (* 10 ms)
Protocol IEC 61850
SICAM_Q100_01
5 %
5 %
5 %
5 %
0.05 %
Setting Range
no
yes
1 to 255
0 to 10
(1 to 6000) * 10 ms
= 10 ms to 60 s
Max. 60 characters
Only a to z, A to Z, _, 0 to 9
are permitted.
The first character must be a
letter.
1 % to 5 %, in 1-% steps
1 % to 5 %, in 1-% steps
1 % to 5 %, in 1-% steps
2 % to 5 %, in 1-% steps
0.02 %
0.05 %
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019