9.5.4

Message Logs

9.5.4.1 Operational Log
To view and clear the Operational log (max. 128), proceed as follows:
NOTE
The last 128 operational indications are displayed, older indications are automatically deleted.
In the navigation window, select the Message Logs menu and click Operational log.
Figure 9-130
Click Delete log in the input/output window.
All operational indications in the input/output window are deleted without backup. The indication no. 0001
appears in the log list: Clear Operational Log.
NOTE
If you need the operational indications, for example for subsequent analysis, save or print them out as
described in chapter 9.2.7.2.
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
Maintenance Tab, Delete Log
9 Operation at Use of a PC
9.5 Maintenance
313