Power Quality
7.10 Mains Signaling Voltage (MSV)
7.10
Mains Signaling Voltage (MSV)
Function Description
7.10.1
Mains signaling voltage (MSV) measurement is performed according to IEC 61000-4-30.
The device detects mains signaling frequencies from 100 Hz to 3 kHz. The threshold for detection and capture
is from 1 % up to 15 % of Un.
Configuration and Value View via the User Interface
7.10.2
Configuration of the Mains Signaling Voltage (MSV)
To change the settings of the MSV in the Configuration tab, proceed as follows:
•
In the navigation window, click Mains signaling voltage.
[sc_q100_MSV, 2, en_US]
Figure 7-24
•
Configure the respective parameters according to the following table.
204
Configuration Tab, Mains Signaling Voltage
SICAM, SICAM Q100 7KG95xx, Manual
E50417-H1040-C522-A9, Edition 06.2021