9.3.3.2 Automation Functions
9.3.3.2.1
Limit Settings
In the Select automation functions menu you can set upper or lower limits for up to 16 measured values. Limit
violations of the upper or lower value range can be output as indications. Limiting value violations can be
signaled at the device via the 2 binary outputs and the LEDs H1 and H2. Furthermore, all 16 limit violations can
be sent to peripheral devices via the communication interfaces.
The programmable limits are divided into two groups Limits 1-8 and Limits 9-16. The parameterization is
identical for all limits.
Default Settings and Setting Ranges of the Limits
Table 9-6
Parameter
Measurement
Limit
Limit type
Hysteresis (%)
Violation indication
1)
31 bytes of UTF-8
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
Limit Settings
Default Setting
-none-
0.0
Lower
1.0
Limit Violation x
(x = 1 to 16)
9 Operation at Use of a PC
9.3 Configuration of the Device
Setting Range
Acc. to list box
(see chapter 16)
-1 000 000 000 to 1 000 000 000 (unit)
Lower
Upper
0.0 to 10.0
Any
1)
Max. 31 characters
175