8 Connection Principle
8.3 Connection Types and Connection Examples
Example 3-Wire Network, 2 Voltage Transformers and 2 Current Transformers, Unbalanced
Figure 8-8
NOTICE
The secondary voltage on terminal F (voltage) must not exceed AC 600 V (AC 347 V for UL).
Non-observance can cause material damage.
Make sure that the maximum permissible phase-to-ground voltage (PE) is not exceeded.
132
PE
S1
S2
a
P1
b
c
Example 3-Wire Network, 2 Voltage Transformers and 2 Current Transformers, Unbalanced
Terminals SICAM Q100
S1
S2
P2
P2
P1
a
b
a
b
A
B
A
B
10 A
10 A
10 A
SICAM Q100, 7KG95xx, Device Manual