Siemens SICAM Q100 7KG95 Series Manual page 242

Class a power quality instrument and power monitoring device
Hide thumbs Also See for SICAM Q100 7KG95 Series:
Table of Contents

Advertisement

9 Operation at Use of a PC
9.3 Configuration of the Device
9.3.7.5.2
Mapping – Measured Values 1-15
At Measured values 1-8 and Measured values 9-15, the measured values are defined which are read by a
selected Modbus slave device.
Default Settings and Setting Ranges of the Modbus Slave Device 1
Table 9-33
Parameter
Name
Unit
Note on frequency measured
values:
If a frequency measured value
(unit: Hz) has been parameterized
without a multiplier (multiplier: -), an
additional check is made whether
the resulting value is in the range of
15 Hz to 65 Hz. Measured values
outside this range are marked as in-
valid.
Register type
Data format on bus
(see also Table 9-34.)
Register number
Scaling factor
1)
If the name is also to be displayed on the device display without text overlappings, Siemens recommends
using max. 10 characters.
242
Settings for assignment of the measured values of the Modbus slave device 1
MV x Slv 1
(x = 1 to 15)
Multiplier: -
Unit: -none-
-none-
Float32 (2 registers)
1
1.000
Default Setting
Max. 31 characters
Acc. to list box
(see chapter 16)
Selecting a multiplier for the following
units is not recommended and will be re-
jected:
-none-
°
°C
°F
%
-none-
Input registers
Holding registers
For -none-, the assignment is ignored
and the corresponding measured value
cannot be selected for other functions.
Float32 (2 registers)
Int16 (1 register)
Int16_Ung8000h (1 register)
UInt16 (1 register)
UInt32 (2 registers)
1 to 65 535
Any float value
0.00: resulting measured value = 0.00
Setting Range
1)
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019