9 Operation at Use of a PC
9.3 Configuration of the Device
9.3.5.2 Tariffs (TOU)
Default Settings and Setting Ranges
Table 9-11Tariffs (TOU)
Parameter
Synchronization source
The following parameters are available only when Synchronization source is set to Calendar.
Season 1 Start
Season 1 End
Season 2 Start
Season 2 End
Weekend Setting
Season x (x = 1 or 2) Tariff
y (y = 1 to 8) Period 1 Start
Season x (x = 1 or 2) Tariff
y (y = 1 to 8) Period 1 End
Season x (x = 1 or 2) Tariff
y (y = 1 to 8) Period 2 Start
Season x (x = 1 or 2) Tariff
y (y = 1 to 8) Period 2 End
Season x (x = 1 or 2) Tariff
y (y = 1 to 8) Period 1 Active
Season x (x = 1 or 2) Tariff
y (y = 1 to 8) Period 2 Active
Season x (x = 1 or 2) Tariff
y (y = 1 to 8) Workday/
Weekend Selection
Coverage Check
1)
In this case, the protocol Modbus TCP can control tariff 1 to tariff 8. Refer to the System Manual SICAM
Q100, chapter 2.2.7.18 Register 0154: Tariffs (read and write), order number E50417-C1040-C522.
2)
This synchronization source can only control tariff 1 or tariff 2.
3)
The default settings of Tariff 1 Period 1 Active for 2 seasons are checked.
186
Default Setting
Protocol
01-01
06-30
07-01
12-31
Thursday and Friday
00:00
24:00
00:00
24:00
3)
No
No
Every Day
Setting Range
1)
Protocol
2)
Binary input 1
2)
Binary input 2
Calendar
01-01 to 12-31
01-01 to 12-31
Not settable
The rest days of the full year
Sunday to Saturday, max. 2 days
00:00 to 23:45
00:15 to 24:00
00:15 to 23:45
00:30 to 24:00
Yes
No
Yes
No
Every Day
Workday
Weekend
Pass
Fail (with gap)
Fail (with overlap)
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019