DS1 and E1 Output Module Default Settings

DS1 and E1 Output Module Default Settings
Table E-9
lists settings and factory defaults for the SSU-2000 DS1 and E1 Output
modules.
Table E-9. DS1 and E1 Output Module Default Settings
Setting
Enable/Disable Outputs
Minimum Clock Level
Bypass Mode
Framing
Line Length
Zero Suppression
Enable/Disable Outputs
Minimum Clock Level
Bypass Mode
Framing
Zero Suppression
CRC
SSM Bit Selection
428 SSU-2000 User's Guide
Factory
Default
DS1 Output Module
Disabled
Settable for each output port
Acquire
Acquire/Lock
ON
ON – Clock C is selected if it is the only one available
OFF – Clock C is not selected even if no other clock is
available
ESF
D4/ESF
0-133 ft
133-266 ft
266-399 ft
399-533 ft
533-655 ft
ON
ON – B8ZS
OFF – AMI
E1 Output Module
Disabled
Settable for each output port
Acquire
Acquire/Lock
ON
ON – Clock C is selected if it is the only one available
OFF – Clock C will not be selected even if no other
clock is available
CAS
CCS/CAS
ON
ON – HDB3
OFF – AMI
ON
ON/OFF
8
Possible SSM bit selection 4, 5, 6, 7, and 8
Range
12713020-002-2 Revision D – April 2004