Using The Hex Number To Identify Output Ports - Symmetricom SSU-2000 User Manual

Synchronization supply unit and the synchronization distribution unit
Hide thumbs Also See for SSU-2000:
Table of Contents

Advertisement

For example, you can provision output ports 1 through 5 for a threshold PQL of 3
and you can disable squelching for ports 6 through 20 (PQL is set to 0). In this
example, if the system PQL is 1, 2, or 3, then ports 1 through 20 generate 2048 kHz
outputs. If the system PQL changes to 4 or higher, then outputs on ports 1 through 5
are squelched (disabled) and ports 6 through 20 continue to generate 2048 kHz
outputs. The response from the Output Status command appears as shown below:
SSU+>out 2a10
2002-12-03T15:30:14 ID: SSU2000 Name:SSU
Module Name: Output 2048 kHz
OUT STATUS
Loc# Type Sta Sel
---- ---- --- ---
2A10 2048 Ok
OUTPUT SETUP
Loc# Type ZS
---- ---- ---- ------ ------
2A10 2048 NA
Output fault action: Leave On
Squelch Level:
P[ 1]= 3, P[ 2]= 3, P[ 3]= 3, P[ 4]= 3, P[ 5]= 3,
P[ 6]= 0, P[ 7]= 0, P[ 8]= 0, P[ 9]= 0, P[10]= 0,
P[11]= 0, P[12]= 0, P[13]= 0, P[14]= 0, P[15]= 0,
P[16]= 0, P[17]= 0, P[18]= 0, P[19]= 0, P[20]= 0,
When the System PQL transitions to a PQL that crosses the user-defined Output-
Squelching PQL threshold, the SSU generates an alarm. The alarm message for
Alarm #14, Squelch, indicates which port(s) are in alarm due to the PQL threshold
being crossed. In the example Alarm message below, Port 20 of the 2048 kHz
Output module is in alarm.
2002-12-12T10:25:26 2A10 Maj Squelch, Below Prov, 00001
A five-digit hexadecimal number (consisting of 20 bits) at the end of the alarm
message identifies the affected port(s). Each digit represents four of the 20 ports on
the module; the first digit represents ports 1 through 4, the second digit represents
ports 5 through 8, and so on, as shown in
Figure 8-10. Using the Hex Number to Identify Output Ports
Table 8-10
lists the failed output port number(s) for each possible hex digit. In the
above alarm message, the hex number is 00001. To determine the port in alarm,
locate the second row (corresponding to Hex Value 1) in
column has an X, which corresponds to Port 20 (read across from Digit 5).
12713020-002-2 Revision D – April 2004
Clk Clk Stat
A B C D Redt Pql 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
-------- ---- --- ------------------------------------------
A
/Y/Y/N/Y
4
MinClk Bypass
ACQ
Off
Port Status
1 1 1 1 1 1 1 1 1 1 2
/S/S/S/S/S/ / / / / / / / / / / / / / / / /
Figure
8-10.
Table
Output Module Reference Data
2048 kHz Output Module
8-10. The right- most
SSU-2000 User's Guide 193