Symmetricom SSU-2000 User Manual page 333

Synchronization supply unit and the synchronization distribution unit
Hide thumbs Also See for SSU-2000:
Table of Contents

Advertisement

ELEVTIME
Use this command to read and set the current time-outs for alarm elevation.
Level 0
Level 1
Level 2
Level 3
Level 4
Remarks
Related
Restrictions None
The following is an example of the ELEVTIME command message format:
SSU_2000->ELEVTIME
SSU_2000->elevtime
2003-06-18T20:44:50Z ID: SSU2000 Name: SSU_2000
1A01 elevation time is 86400 seconds
1A02 elevation time is 86400 seconds
1A03 elevation time is 86400 seconds
1A04 elevation time is 86400 seconds
1A05 elevation time is 86400 seconds
1A08 elevation time is 86400 seconds
1A09 elevation time is 86400 seconds
12713020-002-2 Revision D – April 2004
Not applicable
ELEVTIME [xAy]
If you do not specify a parameter, all module elevation times within
the unit display.
Same as Level 1 operation.
Same as Level 2 operation, with the following additions:
ELEVTIME [xAy] time
Supervisors use this command to read and set the current time-out
length for alarm elevation. The unit is required to elevate MINOR
and MAJOR alarms to the next level after a user settable time
period. Time is in seconds and can be from 60 seconds (1 minute)
to 500,000 seconds.
Same as Level 3 operation
The default value for the elevation time is 86,400 seconds (24
hours).
ALARM,
SETUP
Interactive Command Set
SSU-2000 User's Guide 333