Symmetricom SSU-2000 User Manual page 290

Synchronization supply unit and the synchronization distribution unit
Hide thumbs Also See for SSU-2000:
Table of Contents

Advertisement

TL1 Command Interface
Table B-5. TL1 Retrieve Commands (Continued)
Command
RTRV-PRMTR-CCOUT:[tid]:[aid]:
ctag;
290 SSU-2000 User's Guide
Valid aid code:
,
ALL
SxAy[-z]
This command returns the settings for the composite clock
port designated by the
request, the format for each response message line is:
^^^"aid:mode,level,bypass,pstate,duty,pcomp"<cr lf>
where:
= port access identifier
aid
= CC (composite clock)
mode
= minimum clock level to enable outputs on the
level
module [WARM|ACQ|LOCK]
= allows Clock C selection: [ON|OFF]
bypass
= port state [ON|OFF]
pstate
= duty cycle of the modules outputs [1|0] where 1 =
duty
5/8 and 0 = 50/50
= phase compensation [1 through 7]
pcomp
When no port is specified by the
four lines as follows:
^^^"aid: mode,level,bypass"<cr lf>
^^^"aid:pstate1,pstate2,pstate3,...pstate20"<cr lf>
^^^"aid:duty1,duty2,duty3,...duty20"<cr lf>
^^^"aid:pcomp1,pcomp2,pcomp3,...,pcomp20"<cr lf>
Line 1 contains:
= module access identifier
aid
= CC
mode
= minimum clock level to enable outputs on the
level
module [WARM|ACQ|LOCK]
= allow Clock C selection: [ON|OFF]
bypass
Line 2 contains:
aid = module access identifier
port state [1| 0] (1 = ON, 0 = OFF), where # =
pstate#
port number 1 through 20
Line 3 contains:
= module access identifier
aid
= duty cycle of the module outputs [1|0], where: 1
duty#
= 5/8, 0 = 50/50
= port number 1 through 20
#
Line 4 contains:
= module access identifier
aid
= phase compensation 1 through 7
pcomp#
# = port number 1 through 20
Description
. If a port is specified in the
aid
, then the response is
aid
12713020-002-2 Revision D – April 2004