Table A-5. Output Module Alarm Messages (Continued)
Alarm
Description
Hardware
configuration status
Configuration
mismatch
Loss of clock source
A
Loss of clock source
B
Loss of clock source
C
Loss of clock source
D
No clock selected
VCXO status
Output PLL status
Output fault
12713020-002-2 Revision D – April 2004
Default
Alarm
Alarm
Number
Level
RS-422 Output Module
0
Major
1
Major
2
Major
3
Major
4
Major
5
Major
6
Major
7
Major
8
Major
9
Major
Status
Messages
Ok
Module is installed in an
incorrect slot.
Failed
Ok
Incorrect software loaded
into module.
Invalid
Ok
Clock module in slot A1 is
in warm-up mode or has
Lost
other problems.
Ok
Clock module in slot A12 is
in warm-up mode or has
Lost
other problems.
Ok
Reference signal is in LOS
and both clocks have been
Lost
removed or are in warm-up.
Ok
Only in SDU. Loss of
backup clock. Check cable.
Lost
Ok
No clocks or no clock
output
Below
Selected
VCXO problems, re-seat or
replace module.
Not selected
Ok
No clocks or VCXO.
Re-seat and check clocks.
Lost
Ok
Call Symmetricom Global
Services. Return to factory
Failed
Alarm Messages
Description/
Corrective Action