16.5.3 When "Input (X)", "Output (Y)", "Auxiliary relay (M)" or "State (S)" is selected

"Input (X)", "Output (Y)", "Auxiliary relay (M)" and "State (S)" can be monitored.
"Output (Y)", "Auxiliary relay (M)" and "State (S)" can be tested also.
1. Description of display
[1]
Displayed device
[2]
Displayed device No.
[3]
ON/OFF status of device
*1.
From the displayed device No., the ON/OFF
status of 8 points (in the case of X or Y) or 10
points (in the case of M or S) is indicated.
: OFF status
"Y000" is specified as the device to be displayed, only Y000 and Y003 are
in the ON status.
2. Monitor mode operation
Every time the [+] or [-] button is pressed, the displayed device number is
increased or decreased by "10", and the ON/OFF status is displayed for the
corresponding devices.
To return to the device selection screen, press [ESC] button.
158
Display Content
*1
: ON status
16 Display Module (FX3S-5DM)
[1] [2]
[3]
Y004
[+]
16.5 Monitor/Test
Y000
Y003