MAP 1521: System with Power Failure and No Error Codes

Step 1521-1
For NAS Gateway 500, do the following:
1. Place the system into the service position as described in "Placing the NAS Gateway 500 into the
service position" on page 312.
2. Remove the service access cover as described in "Service access cover removal" on page 314.
You might have been directed to this MAP for one or more of the following reasons:
v The AC power supply power LEDs are not on. The power LEDs on the operator panel and the power
LEDs on the back of the system unit are not blinking. The operator panel is blank.
Go to "Step 1521-2".
v The AC power supply power LEDs are on. Power LEDs, for AC power supplies, on the operator panel
and the back of the system unit are not blinking, and the operator panel is blank. Go to "Step 1521-7"
on page 62.
v The AC power supply power LEDs are on. Power LEDs located on the operator panel and the back of
the system unit are blinking, and OK is displayed on the operator panel.
When the power button, located on the operator panel, is pressed:
– The power LED, located on the operator panel, does not come on.
– None of the cooling fans start to turn.
Go to "Step 1521-7" on page 62.
v The AC power supply power LEDs are on. The power LED, located on the operator panel, is blinking
and OK is displayed on the operator panel.
When the power button on the operator panel is pressed, the power LED, on the operator panel, comes
on and all the fans start to turn.
Go to "Step 1521-7" on page 62.
v An SRN referenced in the RS/6000 Eserver pSeries Diagnostic Information for Multiple Bus Systems
is listed in MAP 1521 in the "Actions/Descriptions" column. Go to "Step 1521-11" on page 63.
Step 1521-2
Is the green power light on the power distribution panel on?
NO
Go to "Step 1521-3".
YES
Go to "Step 1521-5" on page 61.
Step 1521-3
Do the following:
1. Unplug the main power cables from the wall outlet.
2. Because you are servicing a drawer unit that is mounted in a rack, unplug the main power cables from
the power distribution panel.
3. Check that the power cables have continuity.
4. Check that the wall outlet has been wired correctly with the correct voltage.
Did you find a problem?
NO
Go to "Step 1521-4" on page 61.
YES
Correct the problem. Go to "MAP 0410: Repair Checkout" on page 45.
60
NAS Gateway 500 Service Guide