Communication operation and setting
6.23.7

Operation by PLC function (Pr. 414 to Pr. 417, Pr. 498, Pr. 506 to 515)

I/O data read, write, etc. can be performed by accessing the inverter in the predetermined
method using special relays, special registers, etc.
Operation, parameter read/write, etc. can be performed in accordance with the created
sequence programs (built in the inverter) using input data from the control input terminals.
With the output signals, output data can be output to outside the inverter from the control output
terminals as not only the inverter's status signals but also pilot lamp on/off, interlock and other
control signals set freely by the user.
Pr. No. Name
PLC function operation
414
selection
Inverter operation lock
415
mode setting
Pre-scale function
416
selection
417
Pre-scale setting value
PLC function flash
498
memory clear
506
Parameter 1 for user
507
Parameter 2 for user
508
Parameter 3 for user
509
Parameter 4 for user
510
Parameter 5 for user
511
Parameter 6 for user
512
Parameter 7 for user
513
Parameter 8 for user
514
Parameter 9 for user
515
Parameter 10 for user
Refer to the FR-A700 PLC function programming manual for details of the PLC function.
6 - 486
Initial
Setting
Description
Value
Range
0
PLC function is invalid
PLC function is valid
0
1
(Inverter reset is necessary to make this
setting valid.)
The inverter start signal is made valid
0
regardless of the sequence program execu-
tion key.
The inverter start signal is made valid only
when the sequence program execution key
is set to RUN.
0
When the sequence program execution key
1
is in the STOP position, the inverter does
not start if the inverter start signal STF or
STR is turned on. (If the key is switched
from RUN to STOP during inverter opera-
tion, the inverter is decelerated to a stop.)
Pre-scale function selection (increments
scaling factor)
0: No function
1: × 1
0
0 to 5
2: × 0.1
3: × 0.01
4: × 0.001
5: × 0.0001
Set the pre-scale value to calcute the num-
0 to
1
ber of sampling pulse when inputting the
32767
pulse train.
9696: Flash memory clear
0
0 to 9999
Other than 9696:
Flash memory is not cleared
Inverter parameters Pr. 506 to Pr. 515 can
be used as user parameters.
Since this parameter area and the devices
used with the PLC function, D110 to D119,
0 to
are accessible to each other, the values set
0
65535
in Pr. 506 to Pr. 515 can be used in a
sequence program.
The result of operation performed in the
sequence program can also be monitored
using Pr. 506 to Pr. 515.
Parameter
Refer to
Parameters referred to
Section